Electrical Installation Condition Report
Domestic · Periodic inspection and testing to BS 7671
- Reason for the report
- Private rented property — five-yearly check
- Property
- Two-bedroom flat, London (sample)
- Extent
- Whole fixed installation · 100% of circuits tested
- Limitations
- No floor coverings lifted; no fixed furniture moved
- Supply
- TN-C-S · 230 V · Ze 0.18 Ω · Ipf 1.2 kA
- Earthing and bonding
- Earthing 16 mm² · water bonded · gas not bonded
Overall assessment
Unsatisfactory
One observation is coded C2, so the installation is unsatisfactory until it is put right. A landlord must have the work done within 28 days of the inspection (or sooner if the report says so), then send written confirmation, with the report, to the tenant and the council within 28 days of the work being finished.
Observations
- 1 No main protective bonding to the incoming gas pipework. Bonding keeps metal pipes at the same voltage as the earth, so a fault can’t make them dangerous to touch. Potentially dangerous — urgent remedial work needed. C2
- 2 Socket-outlet circuit has no 30 mA RCD (additional protection). Current rules call for RCD protection on sockets. Not dangerous as installed, but improvement is recommended. C3
- 3 Consumer unit enclosure is not made of non-combustible material. Newer boards must be non-combustible. No sign of damage, so improvement is recommended rather than required. C3
Schedule of test results (extract)
| # | Circuit | Device | Cable mm² | R1+R2 Ω | IR MΩ | Zs Ω | RCD ms |
|---|---|---|---|---|---|---|---|
| 1 | Lighting | B6 | 1.0 / 1.0 | 0.62 | >200 | 0.80 | — |
| 2 | Sockets (ring) | B32 | 2.5 / 1.5 | 0.21 | >200 | 0.39 | — |
| 3 | Cooker | B32 | 6.0 / 2.5 | 0.14 | >200 | 0.32 | — |
| 4 | Immersion heater | B16 | 2.5 / 1.5 | 0.28 | >200 | 0.46 | — |
| 5 | Smoke alarms | B6 | 1.0 / 1.0 | 0.55 | >200 | 0.73 | — |
Recommendation
Put right the C2 item, then re-inspect within 5 years